AIRGUARD® EX SPEC 10050
Product description
Part Numbers
10050.01404114, 10050.01405114, 10050.01407114, 10050.01409114, 10050.01412114, 10050.01419114, 10050.01437114, 10050.01204112, 10050.01205112, 10050.01207112, 10050.01209112, 10050.01212112, 10050.01004110
Conductor
- 14 AWG thru 10 AWG annealed bare copper per ASTM B3, Class C stranding per ASTM B8
Insulation
- Flame-retardant Cross-linked Polyethylene (XLPE)
- Color-coded per ICEA Method 1, Table E-2 (does not include white or green)
Ground Conductor(s)
- Annealed stranded tinned copper per ASTM B33
- Single ground wire is sized in accordance with NEC Table 250.122
Shield
- Overall shielded is Flexfoil® aluminum/polymer in contact with stranded tinned copper ground wire
Polymeric Armor
- High strength and high crush-resistant AIRBAG™ layer extruded over the core assembly
Jacket
- Lead-free, flame-retardant, sunlight-resistant Polyvinyl Chloride (PVC)
ApplicationS
- For use in Class I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2 hazardous locations per NEC Articles 501, 502, 503 and 505
- For use as services, feeders and branch circuits for power, lighting, control, and signal circuits in accordance with NEC Articles 330 and 725
- Installed indoors or outdoors, wet or dry locations, directly buried, embedded in concrete, in a raceway, as aerial cable on a messenger, in cable trays, or as exposed runs secured to supports in accordance with NEC Article 330
Features
- Rated at 90°C wet or dry
- Ripcord applied to all cables with a jacket of 60 mils or less
- Meets cold bend test at -40˚C
- Type TC-ER-HL versions exceeds crush and impact requirements of Type MC-HL cables
- Sunlight- and weather-resistant
- Excellent flame resistance
- Excellent physical, thermal and electrical properties
- Excellent moisture resistance
- Good resistance to abrasion and heat deformation
- Provides excellent oil and chemical resistance
Compliances
- Industry Compliances:
- NEC Type XHHW-2 conductors
- UL 1277 Type TC-ER-HL, UL File # E60544/ E83287
- ICEA S-73-532/NEMA WC57
- Flame Test Compliances:
- UL 1685 Vertical Flame Test
- IEEE 1202/FT4
- XHHW-2 inners VW-1
- Other Compliances:
- EPA 40 CFR, Part 261 for leachable lead content per TCLP
- OSHA Acceptable
- RoHS Compliant
Packaging
- Material cut to length and shipped on nonreturnable wood reels