Duralox® Cable - SPEC 7150
Part Numbers
11298.036000, 11298.046000, 11298.036200, 11298.0046200, 11298.0036500, 11298.0046500, 11298.0037000, 11298.0047000, 11298.037500, 11298.047500
Product Construction
Conductors
- 250 kcmil thru 1000 kcmil bare compact copper, Class B stranding per ASTM B496
Insulation
- Cross-linked Polyethylene (XLPE)
- Color-coded per ICEA Method 3, Table E-2
Ground: Annealed bare copper Class B stranding per ASTM B8
Armor: Aluminum Interlocked Armor (AIA)
Jacket: Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armor (GSIA)
Applications
- Ideally suited for use in a broad range of commercial, industrial and utility applications, where maximum performance is demanded, ease of installation is desired, and fire resistance is critical
- Permitted for use per NEC Article 330 - Class I, Division 2 - Class II, Division 2 - Class III, Divisions 1 and 2
- Installed in both exposed or concealed work, wet or dry locations, indoors or outdoors, direct burial and cable trays
Features
- Rated at 90˚C wet or dry
- Provides excellent oil and chemical resistance
- Excellent crush resistance
- Provides a long service life
- Cost-effective alternative to installations in conduit
- Meets cold bend test at -40˚C
- Sunlight-resistant for CT use
Compliances
Industry Compliances
- UL 1569
- UL 44
- ICEA S-95-658/NEMA WC70
- UL Type MC, 600 V or 1000 V, UL File # E90496
- NEC Type XHHW-2 conductors
Flame Test Compliances
- UL 1685 (70,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) CSA FT4
Other Compliances
- EPA 40 CFR, Part 261 for leachable lead content per TCLP method
- OSHA Acceptable
- RoHS Compliant
Packaging
For U.S. customers, material is cut to length and shipped on non-returnable wood reels, while lengths exceeding 10,000 lbs. are provided on returnable steel reels, which require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing.