DuraSheath® Cable - SPEC 6050
Product description
Part Numbers
14901.410805, 14901.410605, 14901.410405, 14901.410205, 14901.410105, 14901.415105, 14901.415205, 14901.415305, 14901.415405, 14901.416005, 14901.416205, 14901.416505, 14901.417005, 14901.417505
Conductor
- 8 AWG thru 1000 kcmil annealed bare copper compact Class B strand
Extruded Strand Shield (ESS)
- Extruded thermoset semi-conducting stress control layer over conductor
Insulation
- Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black jacket material
Jacket
- Lead-Free Cross-linked Chlorinated Polyethylene (XL-CPE)
Applications
- Proven record of reliable performance through extensive use in these applications: pulp and paper mills, petrochemical plants, sewage treatment facilities, water treatment plants, steel mills, textile mills, utility power generating stations, scrubbers and other environmental protection systems, railroad and mining facilities
- For use in industrial and utility applications where ease of installation is a major concern because of limited space and exposure to personnel is minimal
- For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations
Features
- Rated at 90˚C
- Excellent heat, moisture and sunlight resistance
- Flexibility for easy handling
- High dielectric strength
- Low moisture absorption
- Electrical stability under stress
- Low dielectric loss
- Chemical- and sunlight-resistant
- Simplification of splicing and terminating by elimination of need to handle cable shield
- Extra-tough, mechanically rugged composite insulation and jacket construction
- Easy Glider® low friction technology for easy cable pulling
- Meets cold bend test at -35˚C
- 90°C rating for continuous operation
- 130°C rating for emergency overload conditions
- 250°C rating for short circuit conditions
Compliances
- National Electric Code (NEC)
- ICEA S-96-659/NEMA WC71
- UL 1072
- UL listed as Type MV-90 for use in accordance with NEC, UL File # E518856
- Sizes 1/0 AWG and larger are listed and marked “FOR CT USE” in accordance with NEC and also meet IEEE 383 (70,000 BTU/hr)
- Listed “oil-resistant I”
- Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
- OSHA acceptable
Packaging
- Material cut to length and shipped on non-returnable wood reels