SunGen® Photovoltaic Wire - SPEC 5841
Product description
Part Numbers
5841.711200B, 5841.711209B, 5841.711202B, 425440, 439490, 5841.711102B, 5841.710800B, 5841.710809B, 5841.710802B, 5841.710600B, 5841.710400B, 5841.710200B, 5841.710100B, 5841.715100B, 5841.715200B, 5841.715300B, 5841.715400B, 5841.716250B, 5841.716300B, 5841.716350B, 5841.716400B, 5841.716500B, 5841.716600B, 5841.716750B, 5841.717000B, 5841.711200B7, 5841.711209B7, 5841.711202B7, 405400, 439390.06, 439380.06, 405600, 5841.710809B7, 5841.710802B7, 5841.711200, 5841.711209, 5841.711202, 5841.711100, 5841.711109, 5841.711102, 5841.710800, 5841.710809, 5841.710802
Conductor
- 6 AWG thru 2 AWG Class B compact stranded aluminum alloy (8000 Series) per ASTM B800 and ASTM B801
- 1 AWG thru 350 kcmil compact stranded SIW aluminum alloy (8000 Series) per ASTM B800, ASTM B801 and ASTM B836
- 400 kcmil thru 1000 kcmil Class B compact stranded aluminum alloy (8000 Series) per ASTM B800 and ASTM B801
Insulation
- Flame-retardant Cross-linked Polyethylene (XLPE)
- RHH/RHW-2 (XLPE)
Options
- Other sizes and stranding options available upon request
- CT for 1/0 AWG and larger, RHH/RHW-2
- Available in black and full color skin coat
Applications
- Single conductor, sunlight-resistant, direct burial photovoltaic wire rated 90°C wet or dry, 600 V, for interconnection wiring of grounded and ungrounded photovoltaic power systems described in NEC® Article 690
- Stable electrical properties over a broad temperature range
- General purpose building wire for use primarily in conduit or other recognized raceways as specified in the National Electric Code® (NEC®)
- Maximum operating temperature not to exceed 90°C in wet or dry locations
Features
- Oil Resistant PRI/PRII
- Gas and Oil Res GRI/GRII
- UV/sunlight-resistant, moisture-resistant and flame-retardant insulation in all colors
- Meets cold bend and cold impact tests at -40°C
- Excellent electrical, thermal and physical properties
- Resistant to crush, compression cuts and heat deformation
- Rated for direct burial
Compliances
- Industry Compliances: UL 4703 Type PV, UL File #E343277, UL 44 Type RHH or RHW-2, UL File #39406, National Electrical Code (NEC®)
- Flame Test Compliances: UL 2556 Horizontal Burn, CT UL 1685, RHH/RHW-2, VW-1 UL 2556
- Other Compliances: RoHS Compliant, OSHA Acceptable
Packaging
- Material cut to length and shipped on non-returnable wood reels