Anaconda® Type SHD-GC Shielded Round with Ground-Check
Part Numbers
13306.240600, 13306.240400, 13349.340300, 13302.253396, 13301.814577, 13351.179353, 13352.658076, 13349.645300, 13354.490389, 13349.646000, 13349.646100, 13362.315522, 13349.646500
Product Construction
Conductor: 6 AWG thru 500 kcmil coated annealed copper, bunched wires, rope-lay-stranded per ASTM B172
Insulation: Ethylene Propylene Rubber (EPR) insulation
Insulation Shield: A flexible coated copper/textile braid shield is applied over a non-conducting overlapped tape
Ground-Check Conductor: Annealed copper, rope-lay-stranded per ASTM B172, insulated with high-strength yellow polypropylene
Grounding Conductors
- Coated copper, rope-lay-stranded per ASTM B172
- Two conductors in contact with the flexible copper braid shield
Jacket: Reinforced, two-layer, extra-heavy-duty, lead- cured Chlorinated Polyethylene (CPE)
Jacket Marking: PRYSMIAN MI ANACONDA(R) [XX] [AWG/KCMIL] 3/C TYPE SHD-GC 2000 VOLTS (-50C) FT1 FT5 SR CSA LR 27161 P-7K-
102045-2 MSHAA
Options
- Colored jackets are available
- TPU (Thermoplastic Polyurethane) jacket
- Neoprene jacket
Applications
Designed for use as trailing cables on AC mining equipment:
- Where a ground-check conductor is required for fail-safe monitoring
- With Bretby-type cable handling devices on longwall shearers
- Where induced voltages in the grounding system will not produce a hazard
- On low- and medium-voltage AC circuits where shielding is desired or required
Features
- Flexible insulation shield provides shock hazard protection
- Excellent heat, moisture, steam, oil, chemical and radiation resistance
- Flexible for easy handling
- Resists cutting, impact, abrasion, flame and sunlight
- Excellent thermal stability and physical properties over a broad temperature range
- The two-layer jacket is reinforced to provide maximum protection from mechanical damage, the cause of most portable cable failures
Compliances
- ICEA S-75-381 Portable and Power Feeder Cables for use in mines and similar applications
- Meets flame test requirements and is accepted for listing by MSHA
- Approved by the Pennsylvania Department of Environmental Protection
Packaging
Material cut to length and shipped on non-returnable reels