TFFN - SPEC 5280
Product description
Part Numbers
28018, 28016
Conductor
- 18 AWG and 16 AWG fully annealed bare copper per ASTM B3 and B174
Insulation
- Color-coded premium-grade flame-retardant, heat- and moisture-resistant Polyvinyl Chloride (PVC)
Jacket
- Tough Polyamide (Nylon)
Applications
- Internal wiring of fixtures
- Fixture raceways
- Fire alarm circuits in raceways
Features
- Rated Gasoline and Oil Resistant II
- Resistant to abrasion, acids, alkalines, ozone and water
- For TFFN applications, the conductor is appropriate for use in dry locations not to exceed 90°C
- For MTW applications, the conductor is appropriate for use in dry locations at 90°C or not to exceed 60°C in wet locations or where exposed to oil or coolants
- Meets cold bend and cold impact tests at -25˚C
Compliances
- Industry Compliances: ASTM B3 and B174, UL Standard 66 for fixture wire, UL Standard 1063 for machine tool wire (MTW), NFPA 90 (NEC® Article 402), NFPA 79 as appliance wiring material 600 V
- Other Compliances: RoHS Compliant
Packaging
- 4 x 500’ in a carton • 2500’ reels