HVTECK Cable - SPEC 8350
Product description
Part Numbers: 17496.750400, 17469.75200, 17469.75100, 17469.755100, 17469.755200, 17469.755300, 17469.755400, 17469.755600, 17469.756200, 17469.75500, 17469.757000, 17469.757500
Product Construction:
Conductor:
- 6 AWG thru 1000 kcmil bare copper compact Class B strand
Strand Shield:
- A thermoset semi-conducting strand shield is extruded over the conductor
Insulation:
- Tree-Retardant Cross-linked Polyethylene (TRXLPE)
Insulation Shield:
- A semi-conducting thermosetting layer, applied in a triple extrusion process, plus a helically applied gapped copper tape
- Color-coded: black, red or blue colored tape placed longitudinally under the copper tape shield
Ground (Bonding) Conductor:
- The conductor consists of one uninsulated stranded bare copper conductor
Inner Jacket:
- Lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black
Armor:
- Aluminum Interlocked Armor (AIA)
Overall Jacket:
- Lead-free, ACID-FLAME-CHECK √√® flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), orange
Options:
- 105˚C TRXLPE Insulation
- Galvanized Steel Interlocked Armor (GSIA)
Applications:
- For wiring in all hazardous locations when used with certified HL cable glands
- For exposed and concealed wiring in dry, damp or wet locations
- For use in ventilated, non-ventilated and ladder type cable trays in dry, damp or wet locations
- For direct earth burial (with protection as required by inspection authority)
Features:
- Rated at 90˚C wet or dry
- Excellent crush, oil and chemical resistance
- Provides long service life
- Cost-effective alternative to installations in conduit
- Meets cold bend and impact tests at -40˚C
Compliances:
Industry Compliances:
CSA Standard C68.10 MV68.10
Flame Test Compliances:
- CSA FT1 and FT4
- IEEE 1202 (70,000 BTU/hr) CSA FT4
Other Compliances:
- Hazardous Location Rating: HL
- EPA 40 CFR, Part 261 for leachable lead content per TCLP method
- OSHA Acceptable
- RoHS Compliant
Packaging:
- For Canadian customers, lengths are provided on returnable wood or steel reels that require a deposit. Extra charges apply for lagging, pulling eyes, paralleling and plexing
- For U.S. customers, material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing